Triol AK06 Phase Shifting
Hacer un pedidoBeneficios distintivos
20°С … +60°С
Operating temperature range
NEMA4, NEMA4X
Enclosure
Phase shifting autotransformer
PSA
Sobre el producto
IEEE519 standard
Variable Speed Drive AK06 line PS is another complete solution for the efficient control of installations with both induction and permanent magnet motors, as well as for fulfilling the requirements of IEEE519 standard.
Integrated phase-shifting autotransformer,
PS line drives have an integrated phase-shifting autotransformer, which, in combination with 24-pulse rectifier, provides 5% level of harmonic distortion to the input network in the load range from 25% to 100% in accordance with the IEEE 519 standard, and allows operation at frequency supply deviation ±5%.
Especificaciones
Parameter | Value |
---|---|
Power supply, V |
|
Input Frequency, Hz | 50±1 Hz and/or 60±1 Hz |
Rated output current, A | 100 – 2000 |
Overcurrent characteristics | 120% of rated value for 60 sec |
Change of frequency task increment | 0,1 Hz |
Efficiency | 96 % |
Passive filter efficiency | >98 % |
Level of current distortion in the input network THDi,% | <5% in the load range from 25%* to 100% * operation in the extended load range is optional when specified in the order |
DC bus choke | Built-in |
Sine filter | Built-in |
Capacitor unit (for voltage sags) | Option, outdoor
|
Braking IGBT | Option, built-in |
Braking resistor | Option, outdoor |
Electric meter | Option, built-in |
GPRS router | Option, built-in |
PID mode | YES |
HMI |
|
Output frequency |
|
PWM frequency | up to 8 kHz depending on VSD type |
Speed maintenance accuracy (static) | +/- 10% of rated speed in open-loop system |
Control type |
|
Light alarm | “Work”, “Waiting”, “Stop” |
Operator Control Voltage | Option:
|
Number of AI | 2 by default, optional extension +8 |
AI type | programmable 4..20 mA, 0..5 mA, 0..10 V (frequency reference / multifunction analog input) |
Number of DIN | 2 by default, optional extension +4 or more |
DIN type | 24 V, input resistance: 4 kOhm |
Number of analog outputs | Option, 4 or more programmable 4..20 mA, 0..5 mA, 0..10 V |
Number of Relay Outputs | Option, 8 |
Acceleration and deceleration rates |
|
Insulation | Galvanic isolation between power and user circuits |
Insulation resistance | > 5 MOhm |
Protection type |
|
Communication port | Modbus |
Physical interface |
|
Frame Transmission | Modbus RTU |
up to 115200 bps | |
Enclosure protection | NEMA4, NEMA4X |
Material of enclosure | carbon steel, stainless steel |
Operating temperature | -20°С … +60°С (-60°С optional) |
Relative humidity | 100 % |
Cooling type | Air forced |