search clear

Triol AK06 Low Harmonic

Hacer un pedido
Triol AK06  LH

Beneficios distintivos

20°С … +60°С

Operating temperature range

NEMA3R

Enclosure

Built-in

Input harmonic filter

Sobre el producto

Compliance with IEEE519

Variable Speed Drive AK06 line LH is a reliable and profitable solution based on the line RD, for applications that require compliance with the requirements of IEEE519 standard in the main operating range of the installation.

Built-in input harmonic filter

LH drives provide a minimum level of distortion to the input network due to the built-in input harmonic filter. The rated output current of the VSDs is from 100 A to 2000 A, the supply voltage is 380 V, 50 Hz and/or 480 V, 60 Hz. Triol provides efficient control of installations both with induction and valve motors with specialized authoring control algorithms.

Especificaciones

ParameterValue
Power supply, V
  • 3×380 ± 15% / 3×480 (-15% … + 10%)
  • 50% continuously with reduced output power
  • 65% up to 500 ms (with a decrease of output power)
Input Frequency, Hz50±1 and/or 60±1
Rated output current, A100 – 2000
Overcurrent characteristics120% of rated value for 60 sec
Change of frequency task increment, Hz0,1
Efficiency96 %
Passive filter efficiency>98 %
Level of current distortion in the input network THDi<5% in the load range from 25%* to 100%   * operation in the extended load range is optional when specified in the order
DC bus chokeBuilt-in
Sine filterBuilt-in
Capacitor unit (for voltage sags)Option, outdoor


 

Braking IGBTOption, built-in
Braking resistorOption, outdoor
Electric meterOption, built-in
GPRS routerOption, built-in
PID modeYES
HMI
  • UMKA03 controller with a 7-inch monochrome screen, push-button control
  • UMKA07 controller with LCD-TFT 7 inch display, push-button control (touch screen optional)
  • Integration of third-party controller
Output frequency, Hz
  • 1.5 – 80 Hz, in induction motor control mode
  • 1.5 – 200 Hz, in permanent magnet motor control mode
  • 1.5 – 600 Hz, in high-speed PMM control mode

 

PWM frequencyup to 8 kHz depending on VSD type
Speed maintenance accuracy (static) +/- 10% of rated speed in open-loop system
Control type
  • vector control in an open-loop system without speed feedback (for PMM)
  • scalar control: based on the characteristic voltage / frequency U / F (for induction motors)

 

Light alarm“Work”, “Waiting”, “Stop”
Operator Control VoltageOption:


  • 10 V DC, +/- 2% current not more than 30 mA
  • 24 V, 300 mA
  • 110/220 V, 10A for connecting of third-party consumers
Number of AI2 by default, optional extension +8
AI typeprogrammable 4..20 mA, 0..5 mA, 0..10 V (frequency reference / multifunction analog input)
Number of DIN2 by default, optional extension +4 or more
DIN type24 V, input resistance: 4 kOhm
Number of analog outputsOption, 4 or more programmable 4..20 mA, 0..5 mA, 0..10 V
Number of Relay OutputsOption, 8
Acceleration and deceleration rates
  • linear, from 0.1 Hz/s
  • program mode with adjustable time of reaching given frequency
InsulationGalvanic isolation between power and user circuits
Insulation resistance> 5 MOhm
Protection type
  • Overcurrent protection
  • Power switched temperature (IGBT)
  • Max. and min. voltage in the DC link
Communication portModbus
Physical interface
  • 2-wire RS-485/232 for Modbus by default
  • Ethernet (optional) – for communication with ACS /automated control system/
  • wire RS-485/232 for Modbus – for communication with a surface downhole measuring system
Frame TransmissionModbus RTU
up to 115200 bps
Data format8 bits 1 stop bit, no parity
Number of addresses1 .. 255 addresses for Modbus
Access methodslave
Enclosure protectionIP20 (Indoor), NEMA3R
Material of enclosurecarbon steel
Operating temperature-20°С … +60°С (-60°С optional)
Relative humidity95 %
Cooling typeAir forced

Certificados

  • 9001:2015
    9001:2015
  • 61439-1
    61439-1
  • 61000-6-4
    61000-6-4
  • 61000-6-2
    61000-6-2